The Niglon SA123-450 surge protection device is a Type 1 and 2 3 phase SPD.
In summary, a Type 1 SPD is used at the origin of the installation, a Type 2 SPD is used at distribution boards and a Type 3 SPD is used near terminal equipment. ) is lower than the impulse withstand capability of the equipment to be protected.
SA123-450 Type 1+2+3 Surge Protection Device- Pluggable
Description Type 1 + 2 + 3 AC surge protector
Network 230/400 V 3-phase+N
Connection Mode L/N and N/PE
AC system TT/TNS
Max. AC Operating Voltage L-N 275 Vac
Temporary Over Voltage [TOV] Characteristics - 5 sec 180 Vac withstand
Temporary Over Voltage [TOV] Characteristics - 120m 230 Vac disconnection
Temporary Over Voltage N/PE [TOV HT] 1200 v/300A/200ms withstand
Residual Current Leakage Current at Uc None
Follow Current None
Nominal discharge current 15 x 8/20 µs impulses 20kA
Max discharge current max. withstand @ 15 x 8/20µs by pole 50kA
Residual voltage @ In (8/20 µs) 0.6 kV
Protection level L/N @ In (8/20 µs) 1.25 kV
Protection level N/PE @ In (8/20 µs) 1.5 kV
Admissible short-circuit current 25000A
Thermal Disconnector Internal
Fuses Fuse type gG-125A
Installation ground fault breaker Type “S” or delayed
Connection to Network By screw terminals: 2.5-25 mm2
Mounting Symmetrical rail 35mm (EN60715)
Operating Temperature -40/+85˚C
Protection Rating IP20
Housing Material Thermoplastic UL94-V0
Standards of Compliance EN 61645-11, IEC 61643-11, UL1449ed.7
pliance EN 61645-11, IEC 61643-11, UL1449ed.7
Certification EAC CE